Assembly Guide

Types of Backflow Testing

Different hazards call for different assemblies — and each one is tested a different way. Here's what's out there and how we test it.

RP

Reduced Pressure Principle Assembly

Testable — annual
Where it's used
Highest-hazard applications: chemical injection, boilers, car washes, medical and dental, irrigation with fertilizer injection.
How it works
Two independent spring-loaded check valves with a pressure-differential relief valve between them. If either check fouls or pressure reverses, the relief valve opens and dumps water to atmosphere rather than letting it flow backward.
How it's tested
Four test cocks are used to verify check valve #1 and #2 hold tight against backpressure and that the relief valve opens at the required differential (typically 2 psi or more below the #1 check).
DCVA

Double Check Valve Assembly

Testable — annual
Where it's used
Non-health (pollutant) hazards: fire lines without additives, some irrigation, food-grade process lines.
How it works
Two spring-loaded check valves in series, each providing independent protection against backpressure and backsiphonage. No atmospheric relief.
How it's tested
Each check valve is isolated and verified to hold at a minimum 1 psi differential, plus shutoff valves are checked for tightness.
PVB

Pressure Vacuum Breaker Assembly

Testable — annual
Where it's used
The most common lawn irrigation assembly. Must be installed at least 12 inches above the highest downstream outlet.
How it works
A spring-loaded air inlet valve plus a single check valve. Protects against backsiphonage only — not backpressure.
How it's tested
The air inlet must open at 1 psi or higher as pressure drops, and the check valve must hold tight at 1 psi.
SVB

Spill-Resistant Vacuum Breaker

Testable — annual
Where it's used
Indoor or sensitive locations where a standard PVB spilling water during operation is unacceptable.
How it works
Same principle as a PVB but designed so it does not discharge water when the air inlet opens.
How it's tested
Air inlet opening point and check valve tightness are verified, using the assembly's dedicated test cocks and vent.
AVB

Atmospheric Vacuum Breaker

Not testable — inspection only
Where it's used
Simple hose-bibb style and low-hazard applications. No shutoff valve or continuous pressure may be downstream.
How it works
A float or poppet drops to admit air when supply pressure drops. Backsiphonage protection only.
How it's tested
There are no test cocks, so it cannot be field tested. It is visually inspected for correct installation, height and operation.
RPDA / DCDA

Detector Assemblies (Fire Lines)

Testable — annual
Where it's used
Fire sprinkler and standpipe service lines where low-flow leakage or unauthorized use must be detected.
How it works
A full-size RP or DC assembly with a parallel metered bypass containing a smaller assembly, so any small flow registers on the meter.
How it's tested
Both the main assembly and the bypass assembly are tested independently and both must pass.
AG

Air Gap

Not a mechanical assembly
Where it's used
Drain lines, sinks, ice machines, and equipment discharge.
How it works
A physical vertical separation — at least twice the pipe diameter — between the supply outlet and the flood rim. Nothing can be siphoned back across an air gap.
How it's tested
Verified by inspection and measurement; it can be defeated by a hose or extension, so it is checked during a cross-connection survey.

Backpressure vs. Backsiphonage

Backsiphonage happens when supply pressure drops — a water main break or heavy fire-hydrant draw — creating a vacuum that sucks water backward. Backpressure happens when the downstream system is at higher pressure than the supply, such as a pump, boiler or elevated tank pushing water back toward the main. Vacuum breakers stop only backsiphonage; RP and double check assemblies stop both.

409.274.4202